BẢNG SO SÁNH CẤP ĐỘ SẠCH GiỮA TIÊU CHUẨN FS 209E VÀ ISO 14644-1
16/07/2021
QUY CHUẨN LẮP ĐẶT ỐNG GIÓ
02/08/2021

THÔNG SỐ THIẾT KẾ PHÒNG SẠCH CLASS 1, 10, 100

Basic design and operating considerations

Achievable Class*1 and 10 (M1.5 and M2.5)100 (M3.5)
Area per occupant Occupants properly attired Occupant activity Equipment in room Housekeeping40 m2

Full gowns Minimum Minimum Meticulous

30 m2

Full gowns Minimum Minimum Meticulous

Room pressurized Air changes per hour Air lock15 Pa

500-600

Yes

15 Pa

500

Yes

Clean air inlets as % of ceiling area Clean air inlet locations

Terminal velocity at clean air inlet

Return air location

90-100%

Ceiling

0.3 – 0.45 m/s

Perforated floor

90%

Ceiling (wall) 0.3 – 0.45 m/s

Low level or floor

(opposite wall, 0.45 m/s)
Prefilters:

– First stage**

 

30% dust spot efficiency

 

50% dust spot efficiency

F5F5
– Second stage**95% @ 0.3 µm90% dust spot efficiency
H10F9
Prefilter maintenance and inspection

Final filters**

Monthly

Min. 99.9995% on 0.12 µm (for Class 10)

Monthly

Min. 99.999% @ 0.3 um

U15H14
Min. 99.99995% on 0.12 µm (for Class 1)
U16
Routine particle count intervalDailyWeekly

*     Class according to US Federal Standard 209E (between brackets in SI)

** G and F classification in accordance with EN779. H and U classification in accordance with draft EN1822.